• Conductor

    Bare Bunch Copper IS:8130

  • Insulation

    PVC As Per IS:5831

  • Outer Sheath

    PVC As Per IS:5831

  • Cable Standard

    BS 6500, IS 694:2010

  • Operating Temp

    -10°c to max.+90°C

  • Nominal voltage

    1.1 KV

  • Test voltage

    3.0 KV

  • Min. bending radius

    6 x cable diameter

Conductor Insulation Total Thickness of Double Sheath Conductor Resistance at 20°C (max) Current Rating at 40°C
Size of Cable
No. of Wire / Size of Wire
Thickness
Core OD
Thickness
Overall Size
Thickness
Width
Sq. mm.
Nos./mm
mm
mm
mm
mm
mm
Ω/km
Amps.
1.5
22/0.30
0.8
3.25
1.15
6
12.8
12.1
14
2.5
36/0.30
0.9
3.84
1.15
6.4
14.6
7.41
18
4
56/0.30
1
4.5
1.15
7.4
16.8
4.95
26
6
84/0.30
1
5.3
1.15
7.9
18.7
3.3
31
10
140/0.30
1
6.5
1.4
9.9
23.7
1.91
42

The number of wires is approximate and wire diameter is nominal; they shall be such as to satisfy the requirements of conductor resistance as per Class 5 of IEC 60228 / DIN VDE 0295 / IS 8130 / BS 6360

As Per IS:694:2010
Conductor
Insulation
Sheath
Current Rating at 40 C
Size of Cable
No. of Wire / Size of Wire
Thickness
Thickness
Overall Size
Thickness
Width
Sq. mm.
Nos./mm
mm
mm
mm
mm
Amps.
1.5
22/0.30
0.6
0.9
5.2
11.3
14
2.5
36/0.30
0.7
1
6.2
13.3
18
4
56/0.30
0.8
1
7
15.6
26
6
84/0.30
0.8
1.1
7.4
17.7
31

The number of wires is approximate and wire diameter is nominal.

They shall be so as to satisfy the requirements of conductor resistance as per

The number of wires is approximate and wire diameter is nominal.

They shall be so as to satisfy the requirements of conductor resistance as per

Ideal For Irrigation Pumps, Drinking Water Supply Pumps & Submersible Motor Power Supply.